Door opening · insPIRe® CH

Cold room door — vertical section

Cold room door installation in GS insPIRe® CH panel wall — lintel and threshold in a single section. PVC rod-nut system ensures thermal tightness at t > 0°C.

Cold room door — vertical section

Junction function

Cold room door installed in GS insPIRe® CH wall for chambers at temperatures > 0°C (typically +2°C to +8°C — storage of fresh food, pharmaceuticals, fruit).

Critical detail element: the PVC rod-nut fixing system (items 03-05) eliminates the thermal bridge typical of direct steel frame fixing to the panel:

  • Ø10 steel rod (item 05) passes through the panel with PVC insulation (item 03) on both sides.
  • The steel nut (item 06) does not contact the panel — the load is transferred by the PVC nut (item 03).
  • No metal penetrates the full insulation thickness → no water vapour condensation on the nut on the warm side.

Critical installation aspects

  • Ø10 threaded rod (item 05) — galvanised, length = panel thickness + 40 mm (margin for PVC + steel nuts).
  • PVC insulating nut (item 03) — internal steel insert carries the load, external PVC provides thermal insulation.
  • PVC washer (item 04) between panel and steel nut — eliminates point crushing of the panel.
  • Threshold (bottom junction) — door rests on the concrete floor (item 08); bottom frame fixed to the floor with chemical anchors.
  • Plastic sealing compound (item 09) along the perimeter of the frame on both sides — fills minor irregularities, eliminates air leakage.
  • Closing flashing (item 07) covers the frame-panel joint, fixed with fasteners and washers (item 10) every 200 mm.

Chilled vs frozen storage

AspectCold room (this junction, t > 0°C)Freezer (t < 0°C) — see
Fixing systemPVC rod-nut (same)PVC rod-nut (same)
Floorconcrete + resin flooringconcrete + PIR insulation + underfloor heating
Condensation riskmoderate (condensation on warm side)high (condensation + freezing)
Door gasketstandard EPDMfrost-resistant EPDM down to -40°C

Used in the GS insPIRe® CH cold room wall system.

Documentation

Gór-Stal Cold Storage Catalogue 2025, p. 21 — cold room door, vertical section.

Components in this junction

Panel (1)
Flashing (1)
  • 07
    Closing flashing
Accessory (2)
  • 03
    PVC insulating nut with steel insert
  • 04
    PVC mounting washer
Fastener (3)
  • 05
    Galvanised steel threaded rod Ø10
  • 06
    Steel nut M10 with washer Ø21/Ø10.5
  • 10
    Self-drilling fastener for sheet metal or rivet 4.0 × 8.0
Sealant (1)
  • 09
    Permanently plastic sealing compound
Element (2)
  • 02
    Cold room door
  • 08
    Floor as per architectural design