Junction function
Industrial roller door lintel in an A2-s1,d0 wall made of GS MW panels. This is the heaviest opening detail in the hall — door size can range from 4×4 m to 6×6 m, and structural loads on the lintel beam reach several tons.
Three critical requirements:
- Lintel load-bearing structure (item 03) — rolled profile (HEB / IPE) designed by the structural engineer to carry the door weight plus the GS MW panel weight (density 105 kg/m³, 2.5× heavier than PIR).
- Non-combustibility — the system remains A2-s1,d0 within the lintel area; sheet metal flashings must not introduce combustible materials.
- Roller cassette (item 11) — most often inside the wall structure, requires a separate service opening from the interior side.
Critical installation aspects
- OB-20 lintel flashing (item 04) — horizontal masking flashing across the full width of the door opening. Transverse joints (between metre lengths) must always be sealed (items 07, 13) — water from the façade can leak between the flashing and the panel.
- OB-21 side flashing (item 05) — vertical side flashing of the door. Required on each side of the opening. Geometry depends on panel thickness.
- OB-01 corner (item 06) — closes the 90° angle between OB-20 and OB-21 at the 4 corners of the door opening.
- EPDM door gasket (item 08) — between the door frame and OB-20/OB-21. Frost-resistant (down to -40°C), UV-resistant and resistant to greases from the roller mechanism. Standard type BG3.
- PM1 washer (item 10) — eliminates the thermal bridge in the edge zone of the opening where fastener density is doubled.
- Roller cassette (item 11) — usually mounted in the structure above the lintel (not in the MW panel). Requires a dedicated service opening from the hall interior, typically fitted with a metal access door.
Overhead / sectional door vs roller door
| Door type | Lintel structure | Required service zone height |
|---|---|---|
| Roller (this detail) | beam + roller cassette | ~300 mm above the opening |
| Sectional | beam + guide rails | ~600-800 mm above the opening |
| Overhead single-leaf | beam only | none (door frame + jamb) |
Used in systems: GS MW CH wall, GS MW U concealed wall.
Documentation
GS MW catalogue (Gór-Stal, 2025), p. 24 — roller door lintel in mineral wool panels.
Components in this junction
Panel (1)
- 01 GS MW S or CH wall panel
Flashing (3)
- 04 Door lintel flashing OB-20 (OB-20)
- 05 Door side flashing OB-21 (OB-21)
- 06 Corner flashing OB-01 (OB-01)
Accessory (1)
- 10 PM1 mounting washer (PM1)
Fastener (2)
- 09 Self-drilling fastener for sandwich panels
- 12 Self-drilling fastener for sheet metal (washered head)
Sealant (3)
- 07 Self-adhesive PES sealing tape
- 08 EPDM door gasket
- 13 Neutral silicone sealant
Element (3)
- 02 Building structure as per design (steel lintel beam)
- 03 Lintel reinforcement — rolled or welded profile
- 11 Roller door cassette