Junction function
A roof window in a pitched roof is the detail most prone to water leaks and thermal bridging. The structure is complex — the window’s timber frame intrudes into the insulation layer, and 5 functions converge around the window:
- Thermal insulation — termPIR® between rafters + under rafters (W1 variant).
- Windproofing — vapour-permeable membrane on the exterior side.
- Vapour barrier — PE film on the interior side.
- Waterproofing — window collar + roof flashings draining water away.
- Interior finish — plasterboard on framing.
Without careful sealing of all layers around the window perimeter — water ingress, condensation within the insulation, and heat losses increased by 5–8% for the entire building.
Critical installation aspects
- Sealing collar (item 07) — MANDATORY from the window manufacturer (Velux EDW for tile, EBW for sheet metal, FAKRO EZW). Without the collar — a tight installation is impossible.
- Vapour-tight sealing tape BG1 (item 11) around the frame perimeter on the interior side — connects the vapour barrier to the window frame. Class A1 (vapour-tightness).
- Vapour-permeable sealing tape BG3 (item 12) around the frame perimeter on the exterior side — connects the windproofing to the frame. Sd ≤ 0.5 m (vapour permeability).
- Under-rafter insulation min. 40 mm (item 03) around the window frame — in the W1 variant, continuity of insulation requires a termPIR® AL strip on the window frame along all 4 sides. Eliminates the thermal bridge at rafters adjacent to the window.
- Corner zone — at the window corners (4 corners), increased sealing with BG1/BG3 tapes (min. 50 mm overlap) + rigid PVC corner pieces are required.
- Water drainage — the EDW/EZW collar directs water sideways and downwards towards the roof covering, never directly onto the insulation.
Three sealing zones
| Zone | Element | Material |
|---|---|---|
| 1. Exterior (water) | roof flashing + collar | metal + EPDM |
| 2. Middle (wind) | BG3 tape around perimeter | vapour-permeable |
| 3. Interior (vapour) | BG1 tape around perimeter | vapour-tight |
The “3 sealing zones” system — separate tapes with different vapour permeabilities MUST NOT be swapped.
Used in the under-rafter pitched roof system.
Documentation
termPIR® Catalogue — Residential Buildings (Gór-Stal, 2022), p. 25 — roof window in the W1 variant.
Components in this junction
- 02
- 03
- 13 Aluminium tape (tasma-aluminiowa)
- 11 Vapour-tight sealing tape (BG1)
- 12 Vapour-permeable sealing tape (BG3)
- 01 Timber rafter
- 04 PE vapour barrier on the interior side
- 05 Vapour-permeable windproofing membrane
- 06 Roof window frame (timber with aluminium)
- 07 Sealing collar (Velux EDW / FAKRO EZW)
- 08 Roof counter-batten
- 09 Batten
- 10 Roof covering (tile / sheet metal)
- 14 Interior finish (plasterboard on framing)