Wall junction · GS MW

Wall junction — horizontal GS MW S/CH panel layout

Connection of horizontal sandwich panels to masonry / reinforced concrete wall — analogous to vertical layout (p. 23), with different panel fixing geometry. OB-19 flashing + OB-07 internal corner + mineral wool in the gap.

Wall junction — horizontal GS MW S/CH panel layout

Junction function

Wall junction in horizontal layout = analogous structure to the vertical one (p. 21). Geometric difference:

  • Panels terminate at the wall — in horizontal layout panels are longer, so the wall may feature multiple rows of panels, each meeting the masonry.
  • OB-19 + OB-07 flashings continued along the full height of the wall.

All other principles are identical — mineral wool in the gap, masonry waterproofing, verification of geometric deviations in the shell stage.

Critical installation aspects

  • Multi-row panels meeting the masonry — each row requires independent OB-19 fixing to the wall and to the panel.
  • Masonry waterproofing must be continued behind every panel row; without it the strip is left unprotected against water.
  • Mineral wool fills the gap between panels and masonry along the full height; class A1 for fire-resistant walls.
  • Thermal movement of masonry ≠ panels — compensation gap of 5–10 mm to be maintained.

Documentation

Technical Catalogue GS MW S/CH/U (Gór-Stal 2025), page 30 — Wall junction, horizontal layout. Scale 1:5.

Components in this junction

Panel (1)
Insulation (1)
  • 06
    Mineral wool
Flashing (2)
Fastener (2)
  • 07
    Self-drilling fastener for sandwich panels
  • 08
    Self-drilling fastener for sheet metal or 4.0×8.0 rivet
Sealant (1)
  • 05
    PES sealing tape
Element (1)
  • 02
    Masonry and column per structural design