Detail · GS MW

Structural expansion joint — horizontal GS MW S/CH panel layout

Detail of a structural expansion joint in a hall with horizontal panel layout — analogous to the vertical layout (p. 24). Custom flashing absorbing ±20 mm of structural movement, OB-17 cover trim, mineral wool insulation installed on site.

Structural expansion joint — horizontal GS MW S/CH panel layout

Junction function

Expansion joint in horizontal layout = analogous to the vertical layout (p. 22). Required for buildings >60-80 m. Configuration:

  1. Custom expansion flashing (item 03) — flexible Z/Omega element absorbing ±20 mm.
  2. OB-17 cover trim (item 04) conceals the joint from the inside.
  3. On-site mineral wool (item 05) in a 100-200 mm strip, loosely packed.

Full rules = same as the vertical variant (p. 22).

Critical installation aspects

  • Expansion flashing fixed on one side only to the “fixed” structure; the moving side slides relative to the flashing.
  • No rigid fasteners within 50 cm of the expansion joint.
  • Mineral wool loosely packed — remains flexible under movement amplitude.
  • Visual check after the first winter — minor hairline cracks = normal; no movement = flashing poorly designed/fixed.

Documentation

Technical Catalogue GS MW S/CH/U (Gór-Stal 2025), page 33 — Structural expansion joint, horizontal layout. Scale 1:5.

Components in this junction

Panel (1)
Insulation (1)
  • 05
    Thermal insulation installed on site
Flashing (2)
Fastener (2)
  • 07
    Self-drilling fastener for sandwich panels
  • 08
    Self-drilling fastener for sheet metal or 4.0×8.0 rivet
Sealant (1)
  • 06
    PES sealing tape
Element (1)
  • 02
    Steel column and rail framing per structural design