Junction function
The W2 gable wall = identical structural arrangement as W1 (p. 26) but with under-rafter AL GK (item 07) instead of separate termPIR® AL + separate plasterboard. Key principles:
- Fire-resistant ring beam (item 08) — reinforced concrete, REI 60–120 per PN-EN 13501-2.
- termPIR® ETX (item 09) on the outside of the wall — ETICS with ETA 17/0066, class B-s1, d0.
- termPIR® AL between rafters (item 06) + AL GK under rafters (item 07) — continuity of roof insulation onto the wall.
- Additional plasterboard (item 11) on the gable wall from the inside — continuation of the lining from the roof.
Critical installation aspects
- Low-expansion PIR foam (item 12) — fills 5–15 mm gaps around junctions with the ring beam; low-expansion is mandatory (high-expansion foam will disrupt the geometry and create a gap for fire).
- The ring beam (item 08) must extend min. 30 cm above the roof covering (WT § 235); the portion of the ring beam above the covering is covered with galvanised sheet flashing.
- ETX (item 09) — bonded + mechanical installation, in accordance with the technical approval document; full-surface bonding, plate anchors 8 pcs/m² in the edge zone, 6 pcs/m² in the field.
- AL GK board (item 07) cut to fit at the junction with the ring beam — seal with low-expansion PIR foam around the perimeter.
- Additional plasterboard (item 11) on the gable wall — connection to the AL GK on the roof with joint compound + tape; it must be from the same manufacturer’s range (e.g. both Knauf or both Rigips, for matching thickness and texture).
- Screws (item 13) — through the plasterboard substructure → rafters / ring beam; countersink the head 2 mm below the surface, fill as with any plasterboard installation.
Used in the pitched roof — termPIR® under rafters system.
Documentation
Technical Catalogue termPIR® — Residential Buildings (Gór-Stal 2022), page 30 — Pitched roof W II, gable wall detail. Scale 1:10.
Components in this junction
Insulation (3)
- 06 Between-rafter thermal insulation — termPIR® AL board
- 07 Under-rafter thermal insulation — termPIR® AL GK board
- 09 Wall insulation — termPIR® ETX board
Fastener (1)
- 13 Wood screw
Sealant (1)
- 12 Low-expansion polyurethane assembly foam
Element (8)
- 01 Roof covering — roof tiles or metal sheet
- 02 Batten
- 03 Counter-batten (min. 40 mm thick)
- 04 Wind barrier — vapour-permeable membrane
- 05 Timber rafter
- 08 Ring beam closing the fire wall
- 10 Substructure for termPIR® AL GK board
- 11 Plasterboard (additional on the gable wall)