Top floor ceiling — wall plate junction

termPIR insulation continuity at the ceiling / wall plate / knee wall triangle. Critical point for eliminating thermal bridges in unused attic eaves.

Top floor ceiling — wall plate junction

Junction function

Triple-junction point in a single-family house with an unused attic:

  1. Top floor ceiling insulated with termPIR AL/WS (item 12) — insulation laid on the ceiling from the attic side.
  2. External wall insulated with termPIR ETX (item 06) — ETICS system.
  3. Wall plate (item 09) — critical point — timber embedded in the ring beam, a natural thermal bridge trap.

Insulation continuity requires additional wall plate insulation (items 10, 11) — without it, the ring beam / wall plate thermal bridge reduces the ceiling insulation effect by 15-25% (thermographic measurements).

Critical installation aspects

  • Ceiling thermal insulation (item 12) — termPIR AL/WS laid without gaps over the entire ceiling surface, butting up to the knee wall. Boards cut to the slope.
  • Wall plate insulation (item 11) — strip of termPIR AL/WS min. 50 mm thick wrapped around the wall plate (top + side from the attic). Without it, a thermal bridge through the timber.
  • Additional wall plate insulation (item 10) — optional insulation strip between rafters above the wall plate (where the structure allows).
  • Junction with ETX wall insulation (item 06) — termPIR ETX strip overlaps onto the wall plate insulation from the façade side; overlap min. 50 mm.
  • Aluminium tape (item 13) on all board joints — vapour-tightness.
  • PU adhesive (item 14) between individual termPIR layers — mechanical reinforcement + sealing.

Typical U-values

For termPIR AL 200 mm on the ceiling + ETX 150 mm on the wall + 50 mm wall plate insulation:

  • Ceiling: U ≈ 0.12 W/(m²·K)
  • Wall (ETICS): U ≈ 0.16 W/(m²·K)
  • Linear thermal bridge at wall plate Ψ ≈ 0.02 W/(m·K) — with wall plate insulation
  • Without insulation: Ψ ≈ 0.18 W/(m·K) → energy loss 9× greater

Present in systems: top floor ceiling termPIR AL, ETICS wall termPIR ETX.

Documentation

termPIR catalogue — Single-Family Houses, p. 64 — top floor ceiling + wall plate insulation + knee wall.

Components in this junction

Panel (4)
Insulation (1)
  • 16
    Additional insulation material
Accessory (1)
  • 14
    Polyurethane adhesive
Sealant (1)
  • 13
    Aluminium sealing tape
Element (9)
  • 01
    Roof covering — roof tiles or metal sheet
  • 02
    Timber rafter
  • 03
    Batten
  • 04
    Counter-batten
  • 05
    Wind barrier — vapour-permeable membrane
  • 07
    External wall
  • 08
    Reinforced concrete ring beam and ceiling
  • 09
    Wall plate
  • 15
    Plaster