Junction function
The over-rafter roof corner with a gable wall is a three-dimensional building corner — the edge of the pitched roof meets the vertical gable wall (most often triangular). The detail must:
- Close the side edge of termPIR® boards at the gable wall — without this the PIR core would be exposed.
- Ensure continuity of insulation in the 3D corner — without interrupting the insulation of the gable wall and the roof, to avoid a thermal bridge.
- Aesthetic finish of the roof gable edge — OB-31 flashing masks the transition from roof to wall.
The over-rafter system facilitates this junction (vs the between-rafter system) — the insulation is continuous above the rafters, and the counter-batten ends at the gable wall without interrupting the PIR.
Critical installation aspects
- termPIR® AL boards (item 02) cut at the roof angle end at the gable wall line. The edge is sealed with PIR installation foam (item 09) — fills microgaps.
- OB-31 gable flashing (item 07) — finishing of the roof gable edge from the façade side. A 50 mm overlap with the roof covering (tile/sheet metal) is required.
- Aluminium tape (item 08) seals the joints between boards in the gable strip — vapour tightness.
- Gable counter-batten (item 04) — the last counter-batten before the gable wall, fixed with higher screw density (roof edge zone = +50% density).
- Windproof membrane (item 03) overlaps 200 mm onto the gable wall façade finish (item 12) — eliminates wind leakage at the corner.
- Roof-to-wall insulation connection — ideally termPIR® AL (roof) meets termPIR® ETX (ETICS wall) or termPIR® AL (3-layer wall) without a gap — requires careful design and workmanship.
Choice of gable wall finish
| Variant | Wall finish | Connecting flashing |
|---|---|---|
| ETICS wall + termPIR® ETX | silicone render | OB-31 |
| 3-layer wall | clinker / facing brick | OB-31 + brick plinth flashing |
| Façade timber wall | wood / composite | OB-31 + timber drip edge |
Occurs in systems: over-rafter pitched roof, ETICS, 3-layer wall.
Documentation
termPIR® Catalogue — Residential Buildings (Gór-Stal, 2022), p. 20 — over-rafter roof corner.
Components in this junction
- 11 Wall thermal insulation — termPIR® ETX (ETICS) or AL (3-layer)
- 02 termPIR® AL over-rafter boards
- 07 Roof gable flashing (OB-31)
- 08 Aluminium tape (sealing) (tasma-aluminiowa)
- 09 PIR installation foam (edge sealing)
- 01 Gable rafter
- 03 Vapour-permeable windproof membrane
- 04 Gable counter-batten (min. 60×40 mm)
- 05 Batten
- 06 Roof covering (tile / sheet metal)
- 10 Gable wall (masonry with ETICS or 3-layer insulation)
- 12 Gable wall façade finish