PIR Insulation for Ground-Bearing Floors — WT 2021 Guide

PIR Insulation for Ground-Bearing Floors — WT 2021 Guide

Insulating a ground-bearing floor — when to remove old layers and when to add PIR insulation

Upgrading the insulation of a ground-bearing floor in an existing building is one of the toughest decisions in any energy retrofit. On one hand, WT 2021 (Polish Technical Conditions 2021) requires a coefficient of U ≤ 0.30 W/m²K for ground-bearing floors; on the other, every additional centimetre of insulation means losing room height or having to remove existing layers. PIR insulation boards with λD from 0.022 W/(m·K) resolve this conflict — delivering the required thermal performance at a thickness 40–50% smaller than conventional floor-grade EPS.

Two refurbishment scenarios — technical analysis

Variant 1: insulating without removing the existing layers

This approach minimises time and cost, but requires a thorough assessment of:

  • the load-bearing capacity of the existing slab — the old screed must carry service loads together with the new insulation layer, screed and finish,
  • the condition of the damp-proofing — if there is no certainty that the damp-proof barrier is functional, laying another PIR layer will “trap” capillary moisture inside the assembly,
  • a rise in floor level of 12–20 cm (PIR board + new screed + finish) — implying that door frames must be trimmed or replaced, and thresholds, internal stairs and services adjusted.

This variant only makes sense if the existing floor is dry, level and structurally stable. In practice this applies to buildings from the 1990s onwards in which horizontal damp-proofing was executed correctly.

Variant 2: full removal of the old layers

More invasive, but technically safer. It allows you to:

  • install or reinstate the horizontal damp-proofing (torch-on bitumen membrane, EPDM membrane, bitumen-polymer waterproofing),
  • preserve the original room height — critical in heritage buildings and low-ceilinged residential properties,
  • inspect and, if necessary, replace services running within the sub-floor layer (heating, water, drainage).

In deep energy retrofits this is the standard. The cost is higher, but it eliminates the risk of hidden structural defects.

Why PIR boards are the reference material for ground-bearing floors

A ground-bearing floor is an assembly with very specific service loads: constant compression, contact with layers containing technological moisture (screed) and capillary pressure from the ground side. The insulation material must simultaneously meet thermal, mechanical and moisture criteria.

termPIR® WS boards were engineered for these applications — foundations, plinths and ground-bearing floors. They feature increased moisture resistance and stable parameters over time. Alternatively, in classic single-layer assemblies with good damp-proofing, termPIR® AL with its gas-tight aluminium facing works well — provided the continuity of the vapour barrier is maintained (aluminium tape on the joints).

For buildings where minimising assembly thickness is a priority — e.g. commercial premises with limited height — it is worth considering termPIR® MAX 19 AL with λD 0.019 W/(m·K).

Technical parameters relevant to ground-bearing floors

ParameterValueStandard / notes
λD0.022 W/(m·K) (AL); 0.019 (MAX 19)EN 13165
Compressive strength (10% deformation)≥ 120 kPaEN 826
Long-term water absorption< 2% vol.EN 12087
Dimensional stability≤ 1% at 48 h / 70°CEN 1604
Fire reaction classB-s2,d0 (system)EN 13501-1
Standard thicknesses20–250 mm

Sizing the thickness for WT 2021 — required U ≤ 0.30 W/m²K

For a ground-bearing floor the U-value depends not only on insulation thickness, but also on the thermal resistance of the ground and the configuration of the assembly. The values below give an indicative thermal resistance R of the PIR layer alone (without adjacent layers):

termPIR® AL thickness [mm]R [m²K/W]Comment
803.63minimum for new buildings
1004.55optimal for most projects
1205.45energy-efficient standard
1406.36passive standard (with margin)
1506.81recommended for NF15 / passive houses

In practice, once the resistance of the ground and the remaining layers of the assembly is taken into account, a thickness of 100–120 mm of termPIR® AL delivers a U-value of 0.18–0.22 W/m²K — with a safe margin against WT 2021. The detailed system solution is described in ground-bearing floor with termPIR® AL in two layers — a configuration with staggered joints that eliminates thermal bridges at the connections.

PIR/OSB composite — when you need a ready-to-finish substrate

In refurbishments where the floor finish (panels, engineered wood, vinyl) is to be laid directly on top of the insulation, termPIR® AL/OSB is worth considering. The PIR + OSB composite acts simultaneously as a thermal insulation layer and a rigid construction substrate — it eliminates the self-levelling screed step, shortens the construction schedule by several days and significantly reduces the load on the floor structure (important in roof extensions and refurbishment of timber floors).

Installation details — what not to skip

  1. Horizontal damp-proofing — strictly under the PIR layer, regardless of the refurbishment variant. Two layers of torch-on bitumen or an EPDM membrane.
  2. Perimeter expansion strip — 8–10 mm PE tape along vertical walls, eliminating the thermal bridge and accommodating screed movement.
  3. Plinth at the external wall — continuity of thermal insulation between the floor and the foundation insulation — without this, the entire investment in a thick PIR layer is undone by a linear thermal bridge.
  4. Sealing joints with aluminium tape — on Al-faced boards this ensures continuity of the vapour barrier.
  5. TAG (tongue-and-groove) or LAP (rebated) edge profile — the choice of edge profile affects tightness. TAG is recommended for floors.

FAQ — frequently asked questions

What PIR board thickness under a ground-bearing screed is sufficient?

For new buildings subject to WT 2021 (requirement U ≤ 0.30 W/m²K) the technical minimum is 80 mm of termPIR® AL, but 100–120 mm is recommended — this delivers a thermal resistance of 4.5–5.5 m²K/W and a safe design margin. In energy-efficient houses (NF40 / NF15) the standard is 140–150 mm. For comparison: to achieve the same thermal resistance with EPS 100 (λ 0.036) requires a thickness roughly 60–70% greater.

Can PIR boards withstand industrial floor loads?

Standard termPIR® AL and WS boards have a compressive strength of ≥ 120 kPa (at 10% deformation), corresponding to a service load of approximately 12 tonnes/m². For typical residential, office and retail floors with a 50–80 mm screed this is more than sufficient. For industrial floors with forklift trucks and high-bay racking a dedicated board specification should be designed — contact a BOKKA technical advisor.

Can PIR boards be laid directly on old concrete without damp-proofing?

We do not recommend it. Despite the low water absorption of the PIR core (< 2% vol.), the absence of damp-proofing creates a risk of water-vapour condensation at the interface between cold concrete and warm insulation. Horizontal damp-proofing — torch-on bitumen membrane or PE film min. 0.3 mm with sealed overlaps — is required both by standards (PN-B-03002) and from the standpoint of the long-term durability of the entire assembly.

Does termPIR® WS differ from termPIR® AL in thermal performance?

The λD of both boards is comparable (0.022 W/(m·K)). The difference lies in the facing and the application: termPIR® WS has enhanced moisture resistance and is designed for direct contact with layers containing technological water (screeds, damp-proofing). termPIR® AL with its gas-tight aluminium foil works well in assemblies with properly executed horizontal damp-proofing and simultaneously acts as a vapour barrier.

How do you resolve the thermal bridge at the external wall?

The key is to connect the floor insulation with the plinth/foundation insulation. After laying the PIR horizontally, the vapour barrier in the perimeter strip should be carried up onto the wall and connected to the vertical foundation insulation (e.g. termPIR® WS or AL on the plinth). Only such a continuous thermal “capsule” eliminates the linear thermal bridge that, in conventional solutions, generates heat losses of around 0.5–0.8 W/(m·K) per linear metre of external wall.

Planning a thermal upgrade of a ground-bearing floor, or designing a new building? Contact BOKKA’s technical advisors — we will select the PIR board variant, thickness and system solution tailored to your specific project. You will find the full product range in our PIR insulation boards catalogue.