Detail · insPIRe® CH

Mounting of insPIRe® CH panels — negative temperature (t < 0°C)

Horizontal section + A-A of freezer panel mounting to the supporting structure in rooms with temperatures below 0°C. **Thermal insulating PVC fastener system + Ø10 threaded rod** instead of standard steel fasteners — eliminates the thermal bridge critical in freezer rooms.

Mounting of insPIRe® CH panels — negative temperature (t < 0°C)

Junction function

Freezer mounting t < 0°C = a fundamentally different system vs t > 0°C (p. 12). With a temperature gradient of 50-60°C (freezer −25°C + corridor +20°C) you must not use standard steel fasteners — the thermal bridge causes condensation inside the freezer room.

Solution:

  1. Threaded rod Ø10 (item 05) passes through the panel — transfers the structural loads.
  2. PVC insulating nut (item 03) on both sides of the panel — eliminates contact between the steel and the facings.
  3. PVC mounting washer (item 04) distributes the load.
  4. PUR foam + plastic sealant + PES = triple water-vapour sealing.

Critical installation aspects

  • PVC insulating nut ABSOLUTELY REQUIRED — without it, rapid condensation occurs in the freezer room.
  • Ø10 rod = standard; for higher loads (200 mm panels + door weight) → Ø12 must be verified by calculation.
  • Three sealing layers (foam + sealant + PES) = standard for freezer rooms; in cold-storage rooms two may be sufficient.
  • Wall pressure test before handover — critical for HACCP in freezer rooms.

Documentation

Cold-Storage Catalogue GS insPIRe® CH (Gór-Stal 2025), page 21 — Mounting of freezer panels t < 0°C. Scale 1:5.

Components in this junction

Panel (1)
Accessory (2)
  • 03
    PVC insulating nut with steel insert
  • 04
    PVC mounting washer
Fastener (2)
  • 05
    Galvanised steel threaded rod Ø10
  • 06
    Galvanised steel M10 nut + washer
Sealant (3)
  • 07
    Polyurethane assembly foam
  • 08
    Permanently plastic sealant
  • 09
    PES sealing tape
Element (1)
  • 02
    Supporting structure