Wall · insPIRe®

insPIRe® U wall — hidden fix (smooth façade)

Panel with fastener concealed from the façade side — cleaner linear architectural appearance. Choice for representative buildings, office units within halls and architectural façades.

λD
0,022 W/(m·K)
U [W/m²·K]
0,17–0,38
Fire reaction
NRO / B-s1,d0
insPIRe® U wall — hidden fix (smooth façade)

When to use this system

The insPIRe® U panel with hidden fix is the choice when façade aesthetics matter to the design:

  • Office units built into halls — office on the front + production hall at the rear. The front aesthetically articulated, the hall with cheaper S panel.
  • Car showrooms and exhibition spaces — where the façade sells, a smooth surface with no visible fastener heads.
  • New-generation big-box retail — where the façade has to look “lifestyle”, not “warehouse”.
  • Public utility buildings — libraries, offices, schools, where “architectural” façades are specified.

Hidden fix mechanism

In contrast to insPIRe® S (visible joint):

AspectinsPIRe® U (hidden)insPIRe® S (visible)
Screwed fastenerthrough the concealed joint lap, NOT visible from the façade sidethrough the protruding part of the joint, visible heads
Linear façade patterncleaner (no interruptions)broken by fastener heads every 1000/1140 mm
Price per m²+15–20% vs Sbase
Modular widthexclusively 1000 mm1000 or 1140 mm
Thicknesses60–140 mm40–120 mm
Installation speedslower (precise joint seating)faster

Variants

  • insPIRe® U — core λ 0.022 W/(m·K), standard.
  • insPIRe® U MAX — λ reduced to 0.019 (PIR-MAX). U = 0.14 W/m²·K at 140 mm.

Installation requirements

  • Modular width 1000 mm — no 1140 mm variant for U (geometric limitation of the joint).
  • Lengths 2.0–16.0 m (max limited by transport).
  • Hidden fasteners — typically length = panel thickness + 50 mm anchorage in the steel structure.
  • Installation sequence: lower joint precisely engaged into the upper joint of the previous panel → seating → screwing the fastener through the concealed lap.

Required flashings

The cladding system uses a set of flashings matched to the smooth façade:

  • OB-01 / OB-02 — external / internal corner (preferred variants concealing fasteners: OB-03/OB-04)
  • OB-17 — covering the longitudinal panel joint
  • OB-36 — panel closure
  • OB-37 — window sill

Technical documentation

Gór-Stal 2025 Technical Catalogue and Refrigeration Catalogue (p. 5). NRO + B-s1,d0 classification, PZH hygiene certificate, CE acc. to EN 14509:2013.

Layer composition

# Layer Thickness λ Role
1 External facing — S220-S280GD steel sheet + 25 µm coating (L/M/F/R/P profiling) 0.5–0.7 mm external facing
2 PIR / PIR-MAX core (density 40 kg/m³) 60–140 mm 0,022 W/(m·K) main insulation
3 Internal facing — steel sheet + 25 µm coating (L/P profile) 0.4–0.5 mm internal facing

U-value by insulation thickness

termPIR® thickness U [W/m²·K] Meets WT 2021 (roof U ≤ 0.15)
60 mm 0,38 — no
80 mm 0,27 — no
100 mm 0,22 — no
120 mm 0,19 — no
140 mm 0,17 — no